ARMORED CABLES

JACKETED MCACW90/ACWU90600 Volt Copper4 Conductor

Description

Four copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type RW90), phase identified and cabled together with suitable fillers (when necessary) and bare copper ground conductor. Cable core covered with mylar binder tape and galvanized steel interlocked armour, with overall black PVC jacket. Jacket available in colours.

Application

Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2

Standards

UL 1569
​​​​​​​CSA C22.2 #51
ICEA S-95-658/NEMA WC-70
Flame Rated: CT Use, IEEE 383 (70,000 BTU), ICEA T-29-520
       (210,000 BTU), IEEE 1202/CSA FT-4, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -25°C
Sunlight and Oil Resistant II Jacket
Direct Burial (includes encasement in concrete)
Color Code: Method 4 (optional color codes available)
RoHS Compliant

VIEW PRODUCT TABLE DATA

Part Number

 

Size
(AWG or Kcmil)

Strand
(no.)

Insulation

Thickness
(mils)

Grounding

Conductor
(AWG)

Diameter

Over Armour
(in.)

Jacket

Thickness
(mils)

Approx.

Diameter Overall
(in.)

Approx.

Net Weight
(lb./1000')

Ampacity*
(30°C ambient) 90°C Wet/Dry

GAP6/4

6

  7

45

  8

0.87

50

0.97

     769

  75

GAP4/4

4

  7

45

  8

0.99

50

1.09

  1,031

  95

GAP3/4

3

  7

45

  6

1.05

50

1.15

  1,233

115

GAP2/4

2

  7

45

  6

1.13

50

1.23

  1,442

130

GAP1/4

1

19

55

  6

1.33

50

1.43

  1,861

145

GAP1/04

1/0

19

55

  6

1.43

50

1.53

  2,215

170

GAP2/04

2/0

19

55

  6

1.51

60

1.63

  2,666

195

GAP3/04

3/0

19

55

  4

1.65

60

1.77

  3,240

225

GAP4/04

4/0

19

55

  4

1.79

60

1.91

  3,906

260

GAP250/4

250

37

65

  4

1.99

60

2.11

  4,639

290

GAP300/4

300

37

65

  3

2.13

60

2.25

  5,434

320

GAP350/4

350

37

65

  3

2.25

75

2.40

  6,238

350

GAP400/4

400

37

65

  3

2.35

75

2.50

  6,952

380

GAP500/4

500

37

65

  2

2.53

75

2.68

  8,433

430

GAP600/4

600

61

80

  2

2.85

75

3.00

10,052

475

*Per NEC Table 310.15 (B)(16). Four-conductor ampacity assumes three are hot and one is neutral. NOTE: The data shown is approximate and subject to standard industry tolerances.

 

 

REQUEST QUOTE