ARMORED CABLES

JACKETED MCRHW-2/PVC2,000 Volt Copper4 Conductor

Description

Four copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type RHW-2), phase identified and cabled together with suitable fillers (when required) and bare copper grounding conductor. Cable core covered with mylar binder tape and aluminum or galvanized steel interlocked armor with overall black PVC jacket. Jacket available under armor and in colors. Available with EnviroPlus® (LSZH) jacket.

Application

Suitable for use in industrial power distribution systems where continuity of service is the prime consideration. May be installed in wet or dry locations, directly buried, or encased in concrete. Suitable for use in cable tray.

Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2.

Standards

UL 44, UL 854, and UL 1569
ICEA S-95-658/NEMA WC-70
Flame Rated: IEEE 383 (70,000 BTU), ICEA T-29-520 (210,000 BTU),
       IEEE 1202/CSA FT-4, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry
Sunlight Resistant, Gasoline and Oil Resistant II Jacket
Direct Burial (includes encasement in concrete)
Color Code: Black and Numbered (optional color codes available)
RoHS Compliant

VIEW PRODUCT DATA TABLE

Part Number

 

Size
(AWG or Kcmil)

Strand
(no.)

Insulation

Thickness
(mils)

Grounding

Conductor
(AWG)

Diameter

Over Armor
(in.)

PVC Jacket

Thickness
(mils)

Approx.

Diameter Overall
(in.)

Approx.

Net Weight

Aluminum Armor
(lb./1000')

Approx.

Net Weight

Galvanized Armor
(lb./1000')

Ampacity*
(30°C ambient)

AAP2K6/4

6

  7

  85

8

1.07

50

1.17

     778

     924

  75

AAP2K4/4

4

  7

  85

8

1.23

50

1.33

  1,034

  1,195

  95

AAP2K2/4

2

  7

  85

6

1.37

50

1.47

  1,469

  1,737

130

AAP2K1/4

1

  7

105

6

1.57

60

1.69

  1,849

  2,152

145

AAP2K1/04

1/0

19

105

6

1.67

60

1.79

  2,204

  2,531

170

AAP2K2/04

2/0

19

105

4

1.79

60

1.91

  2,672

  3,036

195

AAP2K3/04

3/0

19

105

4

1.89

60

2.01

  3,179

  3,554

225

AAP2K4/04

4/0

19

105

4

2.03

60

2.15

  3,822

  4,231

260

AAP2K250/4

250

37

120

4

2.21

60

2.33

  4,570

  5,011

290

AAP2K350/4

350

37

120

3

2.43

75

2.58

  6,125

  6,626

350

AAP2K500/4

500

37

120

2

2.73

75

2.88

  8,316

  8,887

430

*Per NEC Table 310.15 (B)(16). Four-conductor ampacity assumes three are hot and one is neutral. NOTE: The data shown is approximate and subject to standard industry tolerances.

 