ARMORED CABLES

JACKETED MCXHHW-2/EnviroPlus®600 Volt Copper, LSZH Jacket3 Conductor, Factory Mutual Group 1

Description

Three copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type XHHW-2), phase identified and cabled together with suitable fillers (as necessary) and bare copper ground conductor. Cable core is covered with mylar binder tape and aluminum or galvanized steel interlocked armor with an overall black low smoke, zero halogen, lead-free jacket. Available with tinned conductors.

Application

Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2.

Standards

UL1569
ICEA S-95-658/NEMA WC-70
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4,
       UL 1685 and UL 1581, Two-Hour Firewall
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant
Direct Burial (includes encasement in concrete)
Color Code: Black and Numbered (optional color codes available)
Low Smoke, Zero Halogen Jacket
RoHS Compliant

 

VIEW PRODUCT DATA TABLE

Part Number

 

Size
(AWG or Kcmil)

Strand
(no.)

Insulation

Thickness
(mils)

Grounding

Conductor
(AWG)

Diameter

Over Armor
(in.)

Jacket

Thickness
(mils)

Approx.

Diameter Overall
(in.)

Approx.

Net Weight

Aluminum Armor
(lb./1000')

Approx.

Net Weight

Galvanized Armor
(lb./1000')

Ampacity*
(30°C ambient) 90°C Wet/Dry

AANH8/3

8

  7

45

10

0.73

50

0.83

       405

       489

  55

AANH6/3

6

  7

45

  8

0.81

50

0.91

       547

       643

  75

AANH4/3

4

  7

45

  8

0.91

50

1.01

       733

       854

  95

AANH3/3

3

  7

45

  6

0.97

50

1.07

       889

    1,011

115

AANH2/3

2

  7

45

  6

1.03

50

1.13

    1,044

    1,175

130

AANH1/3

1

19

55

  6

1.15

50

1.25

    1,264

    1,414

145

AANH1/03

1/0

19

55

  6

1.31

50

1.41

    1,548

    1,782

170

AANH2/03

2/0

19

55

  6

1.37

50

1.47

    1,843

    2,110

195

AANH3/03

3/0

19

55

  4

1.51

60

1.63

    2,311

    2,567

225

AANH4/03

4/0

19

55

  4

1.63

60

1.75

    2,785

    3,102

260

AANH250/3

250

37

65

  4

1.75

60

1.87

    3,297

    3,642

290

AANH350/3

350

37

65

  3

1.95

60

2.07

    4,405

    4,807

350

AANH500/3

500

37

65

  2

2.25

60

2.37

    6,049

    6,498

430

AANH600/3

600

61

80

  2

2.45

75

2.60

    7,260

    7,765

475

AANH750/3

750

61

80

  1

2.69

75

2.84

    8,900

    9,449

535

*Per NEC Table 310.15 (B)(16). Four-conductor ampacity assumes three are hot and one is neutral. NOTE: The data shown is approximate and subject to standard industry tolerances.

 

 

REQUEST QUOTE