•  

ARMORED CABLES

FEEDER MCXHHW-2 or RW90600 Volt Copper4 Conductor

Description

Four copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type XHHW-2 or RW90), phase identified and cabled together with suitable fillers (when required) and green or bare ground conductor. Cable core covered with mylar binder tape and aluminum or galvanized steel interlocked armor. Jacket available upon request.

Application

Cost effective replacement for conduit and wire; for service, branch and feeder circuits; and commercial, industrial, and utility applications. For use in theaters (article 520), motion picture and TV studios (article 530), and places of assembly with more than 100 people.

Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2

Standards

UL 1569
CSA C22.2 Type AC90 (with galvanized armor)
ICEA S-95-658/NEMA WC-70
Cable Tray Rated
NEC Article 330 (can be messenger supported)
Flame Rated: Two-hour Firewall
Temperature Rated at 90°C Wet/Dry
Color Code: 120V - BK, WE, RD, BE, GN Ground (#8 AWG-#1 AWG),
       480V (KZ) - BN, GY, OE, YW, GN Ground (#8 AWG-#1 AWG),
       Black and Numbered - Bare Ground (1/0 AWG and larger)
RoHS Compliant

VIEW PRODUCT TABLE DATA

Part Number

 

Size
(AWG or Kcmil)

Strand
(no.)

Insulation Thickness
(mils)

Insulated/Bare

Grounding Conductor
(AWG)

Diameter

Over Armor
(in.)

Approx.

Net Weight

Aluminum Armor
(lb./1000')

Approx.

Net Weight

Galvanized Armor
(lb./1000')

Ampacity*
(30°C ambient) 90°C Wet/Dry

MC8/4

8

  7

45

10

0.89

     416

     517

  55

MC8/4KZ

8

  7

45

10

0.89

     416

     517

  55

MC6/4

6

  7

45

  8

1.03

     591

     730

  75

MC6/4KZ

6

  7

45

  8

1.03

     591

     730

  75

MC4/4

4

  7

45

  8

1.11

     823

     968

  95

MC3/4

3

  7

45

  6

1.23

  1,010

  1,172

115

MC2/4

2

  7

45

  6

1.33

  1,237

  1,491

130

MC1/4

1

19

55

  6

1.43

  1,507

  1,783

145

MC1/04

1/0

19

55

  6

1.43

  1,805

  2,078

170

MC2/04

2/0

19

55

  6

1.51

  2,189

  2,489

195

MC3/04

3/0

19

55

  4

1.65

  2,725

  3,049

225

MC4/04

4/0

19

55

  4

1.79

  3,333

  3,698

260

MC250/4

250

37

65

  4

1.91

  3,967

  4,360

290

MC300/4

300

37

65

  3

2.05

  4,698

  5,115

320

MC350/4

350

37

65

  3

2.17

  5,392

  5,844

350

MC400/4

400

37

65

  3

2.27

  6,078

  6,545

380

MC500/4

500

37

65

  2

2.45

  7,486

  8,003

430

MC600/4

600

61

80

  2

2.71

  8,950

  9,519

475

*Per NEC Table 310.15 (B)(16). Four-conductor ampacity assumes three are hot and one is neutral. NOTE: The data shown is approximate and subject to standard industry tolerances.

 

REQUEST QUOTE