ARMORED CABLES

JACKETED MCXHHW-2/EnviroPlus®600 Volt Copper, LSZH JacketFactory Mutual Group 1

Description

Class B stranded copper conductors, insulated with heat and moisture resistant, chemically crosslinked polyethylene (type XHHW-2), phase identified and cabled together with a **bare copper ground conductor. Cable core is covered with mylar binder tape and aluminum or galvanized steel interlocked armor with an overall black low smoke, zero halogen, lead-free jacket. Available with tinned conductors.

**Cable with seven conductors or more will have a green insulated ground.

Application

Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2.

Standards

UL1569
ICEA S-95-658/NEMA WC-70
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4,
       UL 1685 and UL 1581, Two-Hour Firewall
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant
Direct Burial (includes encasement in concrete)
Color Code: K-2 Solid Colors (optional color codes available)
Low Smoke, Zero Halogen Jacket
RoHS Compliant

 

VIEW PRODUCT DATA TABLE

Part Number

 

Number of

Conductors

 

Grounding

Conductor
(AWG)

Diameter

Over Armor
(in.)

Jacket

Thickness
(mils)

Approx.

Overall Diameter
(in.)

Net Weight
(lb./1000')

Ampacity*
(30°C ambient) 90°C Wet/Dry

AANH14/2

  2

14

0.55

50

0.65

   174

  25†

AANH14/3

  3

14

0.55

50

0.65

   192

  25†

AANH14/4

  4

14

0.55

50

0.65

   210

  20†

AANH14/5

  5

14

0.57

50

0.67

   234

  20†

AANH14/7

  7

14

0.65

50

0.75

   295

  17†

AANH14/9

  9

14

0.73

50

0.83

   352

  17†

AANH14/12

12

14

0.77

50

0.87

   416

12

AANH14/19

19

14

0.89

50

0.99

   573

12

AANH14/37

37

14

1.15

50

1.25

   964

10

 

AANH12/2

  2

12

0.55

50

0.65

   199

  30†

AANH12/3

  3

12

0.55

50

0.65

   226

  30†

AANH12/4

  4

12

0.57

50

0.67

   258

  24†

AANH12/5

  5

12

0.61

50

0.71

   295

  24†

AANH12/7

  7

12

0.71

50

0.81

   381

  21†

AANH12/9

  9

12

0.79

50

0.89

   456

  21†

AANH12/12

12

12

0.85

50

0.95

   551

15

AANH12/19

19

12

0.97

50

1.07

   770

15

AANH12/37

37

12

1.35

50

1.45

1,365

12

 

AANH10/2

  2

10

0.55

50

0.65

   237

  40†

AANH10/3

  3

10

0.59

50

0.69

   287

  40†

AANH10/4

  4

10

0.63

50

0.73

   338

  32†

AANH10/5

  5

10

0.67

50

0.77

   388

  32†

AANH10/7

  7

10

0.79

50

0.89

   505

28

AANH10/9

  9

10

0.89

50

0.99

   611

28

AANH10/12

12

10

0.95

50

1.05

   745

20

AANH10/19

19

10

1.09

50

1.19

1,059

20

AANH10/37

37

10

1.51

60

1.63

1,933

16

*Per NEC Table 310.15 (B)(16) (Ampacity derated in accordance with note 8a). †The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG, and 30 amps for #10 AWG per NEC 310-16 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances.

 