ARMORED CABLES
Three copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type RWU90), phase identified and cabled together with suitable fillers and bare copper grounding conductor. Cable core covered with mylar binder tape and galvanized steel interlocked armour, with overall black PVC jacket. Jacket available in colours. Available with ServiceCPE® jacket.
Suitable for use in industrial power distribution systems where continuity of service is the prime consideration. May be installed in wet or dry locations, directly buried, or encased in concrete. Suitable for use in cable tray.
Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2
UL 44, UL 854, and UL 1569 CSA C22.2 #51 ICEA S-95-658/NEMA WC-70 Flame Rated: IEEE 383 (70,000 BTU), ICEA T-29-520 (210,000 BTU), IEEE 1202/CSA FT-4, Two-hour Firewall Temperature Rated at 90°C Wet /Dry Cold Temperature Rated at -25°C Sunlight and Oil Resistant II Jacket Direct Burial (includes encasement in concrete) Colour Code: Method 4 (optional color codes available) RoHS Compliant
Part Number
Size (AWG or Kcmil)
Strand (no.)
Insulation Thickness (mils)
Grounding Conductor (AWG)
Diameter Over Armour (in.)
Jacket Thickness (mils)
Approx. Diameter Overall (in.)
Approx. Net Weight (lb./1000')
Ampacity* (30°C ambient)
GAP2K6/3
6
7
85
8
0.99
50
1.09
765
75
GAP2K4/3
4
1.19
975
95
GAP2K2/3
2
1.27
1.37
1,427
130
GAP2K1/3
1
105
1.41
1.51
1,718
145
GAP2K1/03
1/0
19
60
1.63
2,044
170
GAP2K2/03
2/0
1.61
1.73
2,432
195
GAP2K3/03
3/0
1.71
1.83
2,843
225
GAP2K4/03
4/0
1.85
1.97
3,358
260
GAP2K250/3
250
37
120
2.05
2.17
4,038
290
GAP2K350/3
350
3
2.27
2.42
5,240
GAP2K500/3
500
2.53
2.68
7,050
430
GAP2K750/3
750
61
135
3.01
3.18
10,093
535
*Per NEC Table 310.15 (B)(16). NOTE: The data shown is approximate and subject to standard industry tolerances.