TRAY & POWER CABLES
Three or four copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type XHHW-2 or RW90), phase identified and cabled together with fillers (when necessary) and bare copper ground conductor. Cable core covered with mylar binder tape, longitudinally applied corrugated copper tape shield and overall black PVC jacket. Available with tinned conductors. Jacket available in colors.
Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2
UL1277 CSA C22.2 #230 TC ICEA S-95-658/NEMA WC-70 Exposed Runs Rated (TC-ER) IMSA 19-1 (K-1 Colors) Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4 Two-hour Firewall Temperature Rated at 90°C Wet/Dry Sunlight and Oil Resistant II Jacket Direct Burial Color Code: Method 4 K-2 Solid Colors (#14 AWG - #10 AWG) (optional color codes available) RoHS Compliant
Part Number
Size (AWG or Kcmil)
Strand (no.)
Insulation
Thickness (mils)
Grounding
Conductor (AWG)
PVC Jacket
Approx.
Diameter Overall (in.)
Net Weight (lb./1000')
Ampacity* (30°C ambient) 90°C Wet/Dry
TCXHSHC14/3G
14
7
30
45
0.40
134
25†
TCXHSHC12/3G
12
0.44
174
30†
TCXHSHC10/3G
10
0.49
232
40†
TCXHSHC8/3G
8
60
0.64
346
55
TCXHSHC6/3G
6
0.72
504
75
TCXHSHC4/3G
4
80
0.87
728
95
TCXHSHC2/3G
2
0.99
1,043
130
TCXHSHC1/3G
1
19
1.10
1,272
145
TCXHSHC14/4G
0.43
157
TCXHSHC12/4G
0.48
207
TCXHSHC10/4G
0.56
294
TCXHSHC8/4G
0.70
424
TCXHSHC6/4G
0.79
617
TCXHSHC4/4G
0.95
901
TCXHSHC2/4G
1.09
1,306
*Per NEC Table 310.15 (B)(16). Four-conductor ampacity assumes three are hot and one is neutral. †The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG and 30 amps for #10 AWG per NEC 310-16 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances.