TRAY & POWER CABLES

TRAY CABLEXHHW-2 or RW90/EnviroPlus®, Shielded600/1,000 Volt Copper, LSZH JacketFactory Mutual Group 1

Description

Class B stranded copper conductors, insulated with heat and moisture resistant, chemically crosslinked polyethylene (type XHHW- 2 or RW90), phase identified and cabled together with fillers (when necessary). Cable core is covered with mylar binder tape, longitudinally applied corrugated copper tape shield, and an overall black low smoke, zero halogen, lead-free jacket. Available with tinned conductors.

Application

Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2.

Standards

UL1277
CSA C22.2 #230/#239 TC/CIC
ICEA S-95-658/NEMA WC-70
Exposed Runs Rated (TC-ER)*
IMSA 19-1 (K-1 Colors)
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4,
       UL1685 and UL 1581, Two-hour Firewall
Temperature Rated 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant
Direct Burial
Color Code: K-2 Solid Colors (optional color codes available)
Low Smoke, Zero Halogen Jacket
RoHS Compliant

VIEW PRODUCT DATA TABLE

 

Part Number

 

 

Number of

Conductors

 

 

Overall

Jacket
(mils)

 

Nominal

Diameter
(in.)

 

Approx.

Net Weight
(lb./1000')

Ampacity
(30°C ambient)
90°C Wet/Dry

TCNHSHC14/2

2

45

0.45

   110

  25†

TCNHSHC14/3

3

45

0.47

   130

  25†

TCNHSHC14/4

4

45

0.50

   154

  20†

TCNHSHC14/5

5

60

0.57

   195

  20†

TCNHSHC14/7

7

60

0.61

   239

  17†

TCNHSHC14/9

9

60

0.69

   292

  17†

TCNHSHC14/12

12

60

0.76

   358

12

TCNHSHC14/19

19

80

0.91

   547

12

 

TCNHSHC12/2

2

45

0.48

   131

  30†

TCNHSHC12/3

3

45

0.51

   163

  30†

TCNHSHC12/4

4

60

0.58

   214

  24†

TCNHSHC12/5

5

60

0.62

   249

  24†

TCNHSHC12/7

7

60

0.67

   311

  21†

TCNHSHC12/9

9

60

0.76

   382

  21†

TCNHSHC12/12

12

80

0.88

   514

15

TCNHSHC12/19

19

80

1.01

   734

15

 

TCNHSHC10/2

2

60

0.56

   181

  40†

TCNHSHC10/3

3

60

0.59

   227

  40†

TCNHSHC10/4

4

60

0.63

   275

  32†

TCNHSHC10/5

5

60

0.68

   324

  32†

TCNHSHC10/7

7

60

0.73

   416

  28†

TCNHSHC10/9

9

80

0.88

   550

  28†

TCNHSHC10/12

12

80

0.98

   696

20

TCNHSHC10/19

19

80

1.12

1,007

20

*Per the NEC, when specified with a separate ground or when one conductor is specified as the cable ground.
†The overcurrent protection for items marked with an (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG, and 30 amps for #10 AWG per NEC 310-16 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances.

 