TRAY & POWER CABLES

TRAY CABLEXHHW-2 or RW90/EnviroPlus®, Shielded600/1,000 Volt Copper, LSZH Jacket3 or 4 Conductor, Factory Mutual Group 1

Description

Three or four copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type XHHW-2 or RW90), phase identified and cabled together with fillers (when necessary) and bare copper ground conductor. Cable core is covered with mylar binder tape, longitudinally applied corrugated copper tape shield, and overall black low smoke, zero halogen, lead-free jacket. Available with tinned conductors.

Application

Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2.

Standards

UL1277
CSA C22.2 #230 TC
ICEA S-95-658/NEMA WC-70
Exposed Runs Rated (TC-ER)
IMSA 19-1 (K-1 Colors)
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4,
       UL1685 and UL 1581, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant
Direct Burial
Color Code: Black and Numbered
       K-2 Solid Colors (#14 AWG - #10 AWG)
       (optional color codes available)

Low Smoke, Zero Halogen Jacket
RoHS Compliant

VIEW PRODUCT DATA TABLE

Part Number

 

Size
(AWG)

Strand
(no.)

Insulation

Thickness
(mils)

Grounding

Conductor
(AWG)

PVC Jacket

Thickness
(mils)

Approx.

Diameter Overall
(in.)

Approx.

Net Weight
(lb./1000')

Ampacity*
(30°C ambient) 90°C Wet/Dry

TCNHSHC14/3G

14

  7

30

14

45

0.40

   136

    25†

TCNHSHC12/3G

12

  7

30

12

45

0.44

   177

    30†

TCNHSHC10/3G

10

  7

30

10

45

0.49

   235

    40†

TCNHSHC8/3G

8

  7

45

10

60

0.64

   352

  55

TCNHSHC6/3G

6

  7

45

  8

60

0.72

   510

  75

TCNHSHC4/3G

4

  7

45

  8

80

0.87

   738

  95

TCNHSHC2/3G

2

  7

45

  6

80

0.99

1,055

130

TCNHSHC1/3G

1

19

55

  6

80

1.10

1,285

145

 

TCNHSHC14/4G

14

  7

30

14

45

0.43

   160

    25†

TCNHSHC12/4G

12

  7

30

12

45

0.48

   210

    30†

TCNHSHC10/4G

10

  7

30

10

60

0.56

   299

    40†

TCNHSHC8/4G

8

  7

45

10

60

0.70

   431

  55

TCNHSHC6/4G

6

  7

45

  8

60

0.79

   624

  75

TCNHSHC4/4G

4

  7

45

  8

80

0.95

   912

  95

TCNHSHC2/4G

2

  7

45

  6

80

1.08

1,320

130

*Per NEC Table 310.15 (B)(16). Four-conductor ampacity assumes three are hot and one is neutral. †The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG, and 30 amps for #10 AWG per NEC 310-16 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances.

 

REQUEST QUOTE