Description

Single copper conductor, stranded and insulated with moisture and heat resistant, chemically crosslinked polyethylene (type XHHW-2) and covered with a sunlight resistant, PVC jacket. Available with tinned conductors. Jacket available in colors.

Standards

UL 44
ICEA S-95-658/NEMA WC-70
Federal Spec. A-A-59544
Flame Rated: CT Use (1/0 AWG and larger)
Temperature Rated at 90°C Wet/Dry
Sunlight Resistant
RoHS Compliant

View Product Data Table

Part Number

 

Size

(AWG or Kcmil)

Strand

(no.)

Insulation Thickness

(mils)

Jacket Thickness

(mils)

Nominal Diameter Overall

(in.)

Approx. Net Weight

(lb./1000')

Ampacity*

(30°C ambient)
90°C Wet/Dry

XHPVC14

14

  7

30

30

0.19

     27

    25†

XHPVC12

12

  7

30

30

0.21

     37

    30†

XHPVC10

10

  7

30

30

0.24

     51

    40†

XHPVC8

8

  7

45

30

0.29

     79

  55

XHPVC6

6

  7

45

30

0.33

   114

  75

XHPVC4

4

  7

45

30

0.38

   169

  95

XHPVC3

3

  7

45

30

0.40

   206

115

XHPVC2

2

  7

45

30

0.43

   253

130

XHPVC1

1

19

55

45

0.52

   331

145

XHPVC1/0

1/0

19

55

45

0.56

   409

170

XHPVC2/0

2/0

19

55

45

0.60

   503

195

XHPVC3/0

3/0

19

55

45

0.65

   620

225

XHPVC4/0

4/0

19

55

45

0.71

   767

260

XHPVC250

250

37

65

65

0.80

   922

290

XHPVC300

300

37

65

65

0.85

1,088

320

XHPVC350

350

37

65

65

0.90

1,253

350

XHPVC400

400

37

65

65

0.95

1,417

380

XHPVC500

500

37

65

65

1.03

1,745

430

XHPVC600

600

61

80

65

1.13

2,090

475

XHPVC750

750

61

80

65

1.23

2,577

535

*Per NEC Table 310.15 (B)(16). †The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG, and 30 amps for #10 AWG per NEC 310-17 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances.

 

REQUEST QUOTE