SINGLE CONDUCTORS
Single copper conductor, stranded and insulated with moisture and heat resistant, chemically crosslinked polyethylene (type XHHW-2) and covered with a sunlight resistant, CPE jacket. Available with tinned conductors.
UL 44 ICEA S-95-658/NEMA WC-70 Federal Spec. A-A-59544 Flame Rated: CT Use (1/0 AWG and larger) Temperature Rated at 90°C Wet/Dry Sunlight Resistant RoHS Compliant
Part Number
Size
(AWG or Kcmil)
Strand
(no.)
Insulation Thickness
(mils)
Jacket Thickness
Nominal Diameter Overall
(in.)
Approx. Net Weight
(lb./1000')
Ampacity*
(30°C ambient) 90°C Wet/Dry
XHCPE14
14
7
30
0.19
27
25†
XHCPE12
12
0.21
37
30†
XHCPE10
10
0.24
51
40†
XHCPE8
8
45
0.29
79
55
XHCPE6
6
0.33
115
75
XHCPE4
4
0.38
169
95
XHCPE3
3
0.40
206
XHCPE2
2
0.43
253
130
XHCPE1
1
19
0.52
332
145
XHCPE1/0
1/0
0.56
409
170
XHCPE2/0
2/0
0.60
504
195
XHCPE3/0
3/0
0.65
621
225
XHCPE4/0
4/0
0.71
768
260
XHCPE250
250
65
0.80
923
290
XHCPE300
300
0.85
1,090
320
XHCPE350
350
0.90
1,255
XHCPE400
400
0.95
1,419
380
XHCPE500
500
1.03
1,746
430
XHCPE600
600
61
80
1.13
2,092
475
XHCPE750
750
1.23
2,579
535
*Per NEC Table 310.15 (B)(16). †The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG, and 30 amps for #10 AWG per NEC 310-17 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances.