SINGLE CONDUCTORS

SERVICEPRO-X®RHW-2 or RWU902,000 Volt Copper, CT RatedNo Pulling Lubricant Required

Description

Single copper conductor, stranded and insulated with moisture and heat resistant, chemically crosslinked polyethylene. Featuring ServicePRO-X® Insulation–No Pulling Lubricant Required (#6 AWG and larger).

Application

Suitable for wiring in raceways, conduit, etc. Applications include general purpose wiring for power distribution, services, feeders, branch circuit wiring in residential, industrial, and commercial buildings. Suitable for use in 105°C dry systems. Also suitable for use in low leakage circuits requiring a dielectric constant of 3.5 or less (Hospital Grade)

Standards

ASTM Standards: B-3 (soft or annealed), B-8 (concentric lay stranded),
       B-787 (combination strand)
UL 44 RHW-2 2kV
ICEA S-95-658/NEMA WC-70
Federal Spec. A-A-59544
Flame Rated: CT Use (1/0 AWG and larger)
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant, Gasoline and Oil Resistant II
Direct Burial
RoHS Compliant

View Product Data Table

Part Number

 

Size

(AWG or Kcmil)

Strand

(no.)

Insulation Thickness

(mils)

Nominal Diameter Overall

(in.)

Approx. Net Weight

(lb./1000')

Ampacity*

90°C Wet/Dry

RWU14BK-NPV

14

  7

  60

0.19

    25

    35†

RWU12BK-NPV

12

  7

  60

0.21

    35

    40†

RWU10BK-NPV

10

  7

  60

0.24

    48

    55†

RWU8BK-NPV

8

  7

  80

0.30

    75

  80

RWU6BK-NPV

6

  7

  80

0.34

  109

105

RWU4BK-NPV

4

  7

  80

0.39

  162

140

RWU3BK-NPV

3

  7

  80

0.41

  198

165

RWU2BK-NPV

2

  7

  80

0.45

  249

190

RWU1BK-NPV

1

19

  95

0.51

  312

220

RWU1/0BK-NPV

1/0

19

  95

0.57

  398

260

RWU2/0BK-NPV

2/0

19

  95

0.59

  481

300

RWU3/0BK-NPV

3/0

19

  95

0.64

  595

350

RWU4/0BK-NPV

4/0

19

  95

0.70

  738

405

RWU250BK-NPV

250

37

110

0.76

  870

455

RWU300BK-NPV

300

37

110

0.81

1,031

500

RWU350BK-NPV

350

37

110

0.86

1,192

570

RWU400BK-NPV

400

37

110

0.91

1,352

615

RWU500BK-NPV

500

37

110

0.99

1,671

700

RWU600BK-NPV

600

61

125

1.09

2,012

780

RWU750BK-NPV

750

61

125

1.17

2,485

885

*Based on ambient temperature of 30°C per NEC Table 310.15 (B)(17). †The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG, and 30 amps for #10 AWG per NEC 310-17 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances.

 

REQUEST QUOTE