TRAY & POWER CABLE

POWER CABLE

MV-105, 133% Jacketed EPR

15,000 Volt Copper

Description

Class B stranded copper, extruded semi-conductor shield, insulated with heat and moisture resistant EPR (133% insulation level), with conductor jacket (PVC, CPE, etc.). Phase identified and cabled with fillers and bare copper ground conductor. Cable core covered with binder tape and overall PVC jacket.
Jacket available in colors.

Standards

UL 1072
ICEA S-93-639/NEMA WC-74
Temperature Rated at 105°C Wet/Dry (conductors)
Sunlight and Oil Resistant II Jacket
Direct Burial
Color Code: K-2 Stripes
RoHS Compliant

ISORoHSUSAREACH
VIEW PRODUCT DATA TABLE

Part Number

 

Size

(AWG or Kcmil)

Strand

(no.)

Conductor

Insulation

Thickness

(mils)

Conductor

Jacket

Thickness

(mils)

Approx. Diameter

Over Single

Conductor

(in.)

Grounding

Conductor

(AWG)

PVC Jacket

Thickness

(mils)

Approx.

Diameter Overall

(in.)

Approx.

Net Weight

(lb./1000')

Ampacity*

(40°C ambient)

P15K2/3EG

2

  7

220

  80

1.04

6

110

2.50

  3,058

165

P15K1/3EG

1

19

220

  80

1.08

4

110

2.59

  3,381

185

P15K1/03EG

1/0

19

220

  80

1.13

4

110

2.70

  3,779

215

P15K2/03EG

2/0

19

220

  80

1.18

4

140

2.86

  4,385

245

P15K4/03EG

4/0

19

220

  80

1.26

3

140

3.04

  5,389

320

P15K250/3EG

250

37

220

  80

1.34

3

140

3.21

  6,090

350

P15K350/3EG

350

37

220

  80

1.44

2

140

3.42

  7,433

430

P15K500/3EG

500

37

220

  80

1.57

1

140

3.70

  9,393

525

P15K750/3EG

750

61

220

110

1.82

1/0

140

4.24

13,020

635

*Per NEC Table 310.60 (C)(75). Based on one three-conductor cable. NOTE: The data shown is approximate and subject to standard industry tolerances.