SERVICEDRIVE®

Description

Three copper conductors, stranded and insulated with heat and moisture resistant, chemically crosslinked polyethylene (type RWU90), phase identified and cabled together with suitable fillers and three symmetrical bare copper ground conductors. Cable core shielded with 5-mil copper tape, helically applied with 50% overlap for 100% coverage and double tape thickness throughout the cable. Standard construction with overall black PVC jacket. Available with CPE or EnviroPlus® (LSZH) jacket. Available with tinned conductors and 50% grounds*.

Application

For use in VFD applications.

Suitable for use in hazardous locations: Class I - Div 2,
       Class II - Div 2, Class III - Div 1 and 2

*Patented for use with ServiceDrive® connector and termination kit.

Standards

CSA C22.2 #230 TC
ICEA S-95-658/NEMA WC-70
Exposed Runs Rated (TC-ER)
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4,
       ICEA T-29-520 (210,000 BTU) (1/0 AWG and larger),
       Two-hour Firewall
Temperature Rated at 90°C Wet/Dry
Sunlight and Oil Resistant II Jacket
Direct Burial
Color Code: Black and Numbered
RoHS Compliant

*U.S. Patent No. 7,309,835

VIEW PRODUCT DATA TABLE

Part Number

 

Size
(AWG or Kcmil)

Strand
(no.)

Insulation Thickness
(mils)

Grounding Conductors
(AWG)

Jacket Thickness
(mils)

Approx. Diameter Overall
(in.)

Approx. Net Weight
(lb./1000')

Ampacity**
(30°C ambient) 90°C Wet/Dry

VFD2KTCP14/3

14

  7

  60

(3) #14

  60

0.55

    208

  25

VFD2KTCP12/3

12

  7

  60

(3) #14

  60

0.59

    245

  30

VFD2KTCP10/3

10

  7

  60

(3) #14

  60

0.64

    295

  40

VFD2KTCP8/3

8

  7

  80

(3) #14

  60

0.79

    415

  55

VFD2KTCP6/3

6

  7

  80

(3) #12

  80

0.91

    638

  75

VFD2KTCP4/3

4

  7

  80

(3) #12

  80

1.02

    843

  95

VFD2KTCP3/3

3

  7

  80

(3) #10

  80

1.07

 1,007

115

VFD2KTCP2/3

2

  7

  80

(3) #10

  80

1.13

 1,177

130

VFD2KTCP1/3

1

19

  95

(3) #10

  80

1.27

 1,439

145

VFD2KTCP1/03

1/0

19

  95

(3) #10

  80

1.35

 1,703

170

VFD2KTCP2/03

2/0

19

  95

(3) #10

  80

1.45

 2,028

195

VFD2KTCP3/03

3/0

19

  95

(3) #8

  80

1.55

 2,481

225

VFD2KTCP4/03

4/0

19

  95

(3) #8

110

1.74

 3,083

260

VFD2KTCP250/3

250

37

110

(3) #8

110

1.88

 3,553

290

VFD2KTCP350/3

350

37

110

(3) #6

110

2.09

 4,753

350

VFD2KTCP500/3

500

37

110

(3) #6

110

2.36

 6,396

430

VFD2KTCP600/3

600

61

125

(3) #6

110

2.58

 7,575

475

VFD2KTCP750/3

750

61

125

(3) #4

140

2.81

9,441

535

**Per NEC Table 310.15 (B)(16). NOTE: The data shown is approximate and subject to standard industry tolerances.

 