SINGLE CONDUCTORS

SERVICESOLAR® (PV)RHW-2600 Volt CopperNo Pulling Lubricant Required

Description

Single copper conductor, stranded and insulated with moisture and heat resistant, chemically crosslinked polyethylene. Featuring ServicePRO-X® Insulation–No Pulling Lubricant Required (#6 AWG and larger). Rated 600V to meet the challenging requirements of transformerless inverters on photovoltaic (solar) panel installations. Available in colors.

Application

Suitable for use as interconnection wiring on solar panels in grounded or ungrounded systems as defined in applicable parts of the National Electrical Code (NEC) NFPA 70, such as article 690.31(A). Suitable for use in 105°C dry systems. Also suitable for use in low leakage circuits requiring a dielectric constant of 3.5 or less (Hospital Grade).

Standards

ASTM Standards: B-3 (soft or annealed), B-8 (concentric lay stranded)
       B-787 (combination strand)
UL 44 RHW-2, UL 854 USE-2, and UL 4703 PV Wire
C(UL) RPVU90 1kV/2kV: CSA C22.2 #271
ICEA S-95-658/NEMA WC-70
Federal Spec. A-A-59544
Flame Rated: Vertical Wire, CT Use (1/0 AWG and larger)
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant, Gasoline and Oil Resistant II
Direct Burial
RoHS Compliant

View Product Data Table

Part Number

 

Size

(AWG or Kcmil)

Strand

(no.)

Insulation Thickness

(mils)

Nominal Diameter Overall

(in.)

Approx. Net Weight

(lb./1000')

Ampacity*

90°C Wet/Dry

PV14BK

14

  7

  60

0.19

     25

    35†

PV14BK-C

14

19

  60

0.19

     25

    35†

PV12BK

12

  7

  60

0.21

     34

    40†

PV12BK-C

12

19

  60

0.21

     34

    40†

PV10BK

10

  7

  60

0.24

     48

    55†

PV10BK-C

10

19

  60

0.24

     48

    55†

PV8BK

8

  7

  75

0.29

     75

  80

PV8BK-C

8

19

  75

0.29

     75

  80

PV6BK

6

  7

  75

0.33

   109

105

PV4BK

4

  7

  75

0.38

   162

140

PV3BK

3

  7

  75

0.40

   198

165

PV2BK

2

  7

  75

0.43

   243

190

PV1BK

1

19

  95

0.51

   316

220

PV1/0BK

1/0

19

  95

0.55

   389

260

PV2/0BK

2/0

19

  95

0.59

   481

300

PV3/0BK

3/0

19

  95

0.64

   595

350

PV4/0BK

4/0

19

  95

0.70

   738

405

PV250BK

250

37

110

0.79

   875

455

PV300BK

300

37

110

0.85

1,037

500

PV350BK

350

37

110

0.90

1,198

570

PV400BK

400

37

110

0.94

1,358

615

PV500BK

500

37

110

1.02

1,676

700

PV600BK

600

61

125

1.14

2,021

780

PV750BK

750

61

125

1.24

2,497

885

*Based on ambient temperature of 30°C per NEC Table 310.15 (B)(17). †The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG, and 30 amps for #10 AWG per NEC 310-17 footnote. NOTE: Photovoltaic module interconnection wire for use with or without a raceway in accordance with wiring systems Article 690 in the National Electrical Code (NEC), NFPA 70. NOTE: The data shown is approximate and subject to standard industry tolerances.

 