•  

TRAY & POWER CABLES

POWER CABLEMV-105, Shielded5,000 Volt Copper

Description

Three Class B stranded copper conductors, phase identified and cabled together with fillers (when necessary) and bare copper ground conductor. Cable core covered with mylar binder tape and overall PVC jacket (other jackets available upon request). Jacket available in colors.

Shielded: Class B stranded copper with extruded semi-conductor shield,
insulated with heat and moisture resistant EPR (5kV rated - 133% insulation
level; 8kV rated - 100% insulation level) with conductor jacket.

Standards

UL 1072
Non-shielded: ICEA S-96-659/NEMA WC-71
Shielded: ICEA S-93-639/NEMA WC-74
Conductors Rated at 105°C
Sunlight Resistant, Gasoline and Oil Resistant II Jacket
Direct Burial
Color Code: K-2 Stripes
RoHS Compliant

VIEW PRODUCT DATA TABLE

Part Number

 

Size
(AWG or Kcmil)

Strand
(no.)

Conductor

Insulation

Thickness
(mils)

Conductor

Jacket

Thickness
(mils)

Approx.

Diameter Over

Single Cond.
(in.)

Grounding

Conductor
(AWG)

PVC Jacket

Thickness
(mils)

Approx.

Diameter Overall
(in.)

Approx.

Net Weight
(lb./1000')

Ampacity*
(40°C ambient)

P5KS4/3EG

4

  7

115

  60

0.73

6

110

1.83

  1,775

100

P5KS2/3EG

2

  7

115

  60

0.78

6

110

1.94

  2,115

135

P5KS1/3EG

1

19

115

  60

0.82

4

110

2.03

  2,491

155

P5KS1/03EG

1/0

19

115

  80

0.91

4

110

2.22

  2,908

185

P5KS2/03EG

2/0

19

115

  80

0.96

4

110

2.33

  3,301

210

P5KS4/03EG

4/0

19

115

  80

1.05

3

110

2.52

  4,324

285

P5KS250/3EG

250

37

115

  80

1.11

3

110

2.65

  4,872

315

P5KS350/3EG

350

37

115

  80

1.21

2

140

2.93

  6,289

390

P5KS500/3EG

500

37

115

  80

1.36

1

140

3.25

  8,244

475

P5KS750/3EG

750

61

115

  80

1.55

1/0

140

3.66

11,350

585

*Per NEC Table 310.60 (C)(75). Based on one three-conductor cable. NOTE: The data shown is approximate and subject to standard industry tolerances.

 

REQUEST QUOTE