ARMORED CABLES

MV-105133% Jacketed EPR15,000 Volt Copper

Description

Three stranded copper conductors with extruded semi-conductor shield, insulated with heat and moisture resistant EPR (133% insulation level) with conductor jacket. Phase identified and cabled together with fillers and bare copper ground conductor. Cable core covered with mylar binder tape, aluminum or galvanized steel interlocked armor, and red PVC jacket (other jackets available upon request). Jacket available under armor and in colors.

Application

Suitable for use in hazardous locations: Class I - Div 2.

Standards

UL 1072
ICEA S-93-639/NEMA WC-74
Flame Rated: IEEE 383 (70,000 BTU), ICEA T-29-520 (210,000 BTU),
       IEEE 1202/CSA FT-4
Temperature Rated at 105°C Wet/Dry (conductors)
Sunlight Resistant, Gasoline and Oil Resistant II Jacket
Direct Burial (includes encasement in concrete)
Color Code: K-2 Stripes
RoHS Compliant

VIEW PRODUCT DATA TABLE

Part Number

 

Size
(AWG or Kcmil)

Strand
(no.)

Conductor

Insulation

Thickness
(mils)

Conductor

Jacket Thickness
(mils)

Grounding

Conductor
(AWG)

Diameter

Over Armor
(in.)

PVC Jacket

Thickness
(mils)

Approx.

Diameter Overall
(in.)

Approx.

Net Weight

Aluminum Armor
(lb./1000')

Approx.

Net Weight

Galvanized Armor
(lb./1000')

Ampacity*
(40°C ambient)

AP15K2/3E

2

  7

220

  80

6

2.57

75

2.72

  2,987

  3,527

145

AP15K1/3E

1

19

220

  80

4

2.65

75

2.80

  3,298

  3,861

165

AP15K1/03E

1/0

19

220

  80

4

2.77

75

2.92

  3,674

  4,243

195

AP15K2/03E

2/0

19

220

  80

4

2.85

75

3.00

  4,083

  4,692

220

AP15K4/03E

4/0

19

220

  80

3

3.09

85

3.26

  5,100

  5,733

290

AP15K250/3E

250

37

220

  80

3

3.21

85

3.38

  6,180

  6,872

315

AP15K350/3E

350

37

220

  80

2

3.41

85

3.58

  7,507

  8,246

385

AP15K500/3E

500

37

220

  80

1

3.69

85

3.86

  9,878

10,682

470

AP15K750/3E

750

61

220

110

1/0

4.21

85

4.38

13,610

14,537

570

*Per NEC Table 310.60 (C)(75). Based on one three-conductor cable. NOTE: The data shown is approximate and subject to standard industry tolerances.

 

REQUEST QUOTE