SINGLE CONDUCTOR

XHHW-2/PVC

600/1,000 Volt Copper

Description

Single copper conductor, stranded, insulated with moisture and heat resistant, chemically crosslinked polyethylene (type XHHW-2) and covered with a sunlight resistant, PVC jacket. Available with tinned conductors. Jacket available in colors.

Standards

UL 44
ICEA S-95-658/NEMA WC-70
Federal Spec. A-A-59544
Flame Rated: CT Use (1/0 AWG and larger)
Temperature Rated at 90°C Wet/Dry
Sunlight Resistant
RoHS Compliant

ISOROHSUSAREACH
View Product Data Table

Part Number

 

Size

(AWG or Kcmil)

Strand

(no.)

Insulation Thickness

(mils)

Jacket Thickness

(mils)

Nominal Diameter Overall

(in.)

Approx. Net Weight

(lb./1000')

Ampacity*

(30°C ambient) 90°C Wet/Dry

XHPVC14

14

7

30

30

0.19

     27

    25†

XHPVC12

12

7

30

30

0.21

     37

    30†

XHPVC10

10

7

30

30

0.24

     51

    40†

XHPVC8

8

7

45

30

0.29

     79

  55

XHPVC6

6

7

45

30

0.33

   114

  75

XHPVC4

4

7

45

30

0.38

   169

  95

XHPVC3

3

7

45

30

0.40

   206

115

XHPVC2

2

7

45

30

0.43

   253

130

XHPVC1

1

19

55

45

0.52

   331

145

XHPVC1/0

1/0

19

55

45

0.56

   409

170

XHPVC2/0

2/0

19

55

45

0.60

   503

195

XHPVC3/0

3/0

19

55

45

0.65

   620

225

XHPVC4/0

4/0

19

55

45

0.71

   767

260

XHPVC250

250

37

65

65

0.83

   929

290

XHPVC300

300

37

65

65

0.89

1,096

320

XHPVC350

350

37

65

65

0.94

1,262

350

XHPVC400

400

37

65

65

0.98

1,426

380

XHPVC500

500

37

65

65

1.06

1,752

430

XHPVC600

600

61

80

65

1.18

2,103

475

XHPVC750

750

61

80

65

1.28

2,589

535

*Per NEC Table 310.15 (B)(16). †The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG and 30 amps for #10 AWG per NEC 310-17 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances.