SINGLE CONDUCTOR

USE-2/RHW-2/RW90

CT Rated

600/1,000 Volt Copper

Description

Single copper conductor, stranded and insulated with moisture and heat resistant, chemically crosslinked polyethylene. Available in colors.

Application

Suitable for use in general purpose wiring applications and may be installed in raceway, conduit, direct burial and aerial installations where a cable having superior flame retardance is required. Suitable for use in 105°C dry systems. Also suitable for use in low leakage circuits requiring a dielectric constant of 3.5 or less (Hospital Grade).

Standards

ASTM Standards: B-3 (soft or annealed), B-8 (concentric lay stranded),
       B787 (combination strand)
UL 44 and UL 854, C(UL)US RW90 1kV: CSA/UL Listed, C(UL) RPV90 600V
CSA C22.2 No. 38
ICEA S-95-658/NEMA WC-70
L-824C (#12 AWG - 4/0 AWG)
Federal Spec. A-A-59544
Flame Rated: CT Use (1/0 AWG and larger)
Temperature Rated at 90°C Wet/Dry
Cold Temperature Rated at -40°C
Sunlight Resistant, Gasoline and Oil Resistant II
Direct Burial
RoHS Compliant

ISOROHSUSAREACH
View Product Data Table

Part Number

 

Size

(AWG or Kcmil)

Strand

(no.)

Insulation Thickness

(mils)

Approx. Diameter Overall

(in.)

Aprox. Net Weight

(lb./1000')

Ampacity

90ºC Wet/Dry

USE14BK

14

  7

  45

0.163

    21

    35†

USE12BK

12

  7

  45

0.182

    30

    40†

USE10BK

10

  7

  45

0.205

    43

    55†

USE8BK

8

  7

  60

0.263

    69

  80

USE6BK

6

  7

  60

0.301

  103

105

USE4BK

4

  7

  60

0.350

  156

140

USE3BK

3

  7

  60

0.374

  192

165

USE2BK

2

  7

  60

0.404

  238

190

USE1BK

1

19

  80

0.476

  307

220

USE1/0BK

1/0

19

  80

0.517

  384

260

USE2/0BK

2/0

19

  80

0.562

  476

300

USE3/0BK

3/0

19

  80

0.610

  590

350

USE4/0BK

4/0

19

  80

0.669

  735

405

USE250BK

250

37

  95

0.762

  868

455

USE300BK

300

37

  95

0.819

1,031

500

USE350BK

350

37

  95

0.866

1,192

570

USE400BK

400

37

  95

0.911

1,353

615

USE500BK

500

37

  95

0.986

1,673

700

USE600BK

600

61

110

1.111

2,033

780

USE750BK

750

61

110

1.205

2,493

885

*Per NEC Table 310.15 (B)(17). †The overcurrent protection for items marked with an obelisk (†) shall not exceed 15 amps for #14 AWG, 20 amps for #12 AWG, and 30 amps for #10 AWG per NEC 310-17 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances.