SERVICEDRIVE®

ASD/VFD TRAY CABLE

XHHW-2 or RW90/PVC, Shielded

600 Volt Copper

Patented for use with ServiceDrive® connector and termination kit.

Description

3 conductors, stranded, insulated with heat and moisture resistant crosslinked polyethylene (type XHHW-2 or RW90), phase identified and cabled with suitable fillers and 3 symmetrical bare copper ground conductors. Cable core covered with 5-mil helical copper tape shield, and overall black PVC jacket. Available with tinned conductors. Jacket available in colors.

Application

For use in ASD/VFD applications.

Suitable for use in hazardous locations: Class I - Div 2,
       Class II - Div 2, Class III - Div 1 and 2

Standards

UL 1277, CSA C22.2 #230 TC
ICEA S-95-658/NEMA WC-70
Exposed Runs Rated (TC-ER) (#4 AWG and larger)
Flame Rated: IEEE 383 (70,000 BTU), ICEA T-29-520 (210,000 BTU)
       (1/0 AWG and larger)
, IEEE 1202/CSA FT-4, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry
Sunlight and Oil Resistant II Jacket
Direct Burial
Code: Method 4
RoHS Compliant

ISORoHSUSAREACHRockwell
VIEW PRODUCT DATA TABLE

Part Number

 

Size

(AWG or Kcmil)

Strand

(no.)

Insulation Thickness

(mils)

Grounding Conductors

(AWG)

PVC Jacket Thickness

(mils)

Approx. Diameter Overall

(in.)

Approx. Net Weight

(lb./1000')

Ampacity*

(30°C ambient) 90°C Wet/Dry

ASDTCP14/3

14

  7

45

3-#10

  60

0.57

   274

  25

ASDTCP12/3

12

  7

45

3-#10

  60

0.59

   305

  30

ASDTCP10/3

10

  7

45

3-#10

  60

0.62

   351

  40

ASDTCP8/3

8

  7

45

3-#10

  60

0.64

   415

  55

ASDTCP6/3

6

  7

45

3-#10

  60

0.72

   539

  75

ASDTCP4/3

4

  7

45

3-#10

  80

0.87

   762

  95

ASDTCP3/3

3

  7

45

3-#10

  80

0.92

   889

115

ASDTCP2/3

2

  7

45

3-#8

  80

0.98

1,103

130

ASDTCP1/3

1

19

55

3-#8

  80

1.09

1,332

145

ASDTCP1/03

1/0

19

55

3-#6

  80

1.18

1,677

170

ASDTCP2/03

2/0

19

55

3-#6

  80

1.28

1,991

195

ASDTCP3/03

3/0

19

55

3-#4

  80

1.38

2,513

225

ASDTCP4/03

4/0

19

55

3-#4

  80

1.51

3,004

260

ASDTCP250/3

250

37

65

3-#4

110

1.75

3,562

290

ASDTCP350/3

350

37

65

3-#2

110

1.97

4,876

350

ASDTCP500/3

500

37

65

3-#1

110

2.23

6,638

430

ASDTCP600/3

600

61

80

3-1/0

110

2.49

8,018

475

ASDTCP750/3

750

61

80

3-2/0

110

2.70

9,846

535

*Per NEC Table 310.15 (B)(16). NOTE: The data shown is approximate and subject to standard industry tolerances.