SERVICEDRIVE®

ASD/VFD JACKETED MC

XHHW-2 or RW90/PVC

600 Volt Copper

Patented for use with ServiceDrive® connector and termination kit.

Description

3 conductors, stranded, insulated with heat and moisture resistant crosslinked polyethylene (type XHHW-2 or RW90), phase identified and cabled with suitable fillers and 3 symmetrical copper ground conductors. Cable core covered with binder tape, 5-mil helical copper tape shield and galvanized steel interlocked armor with overall PVC jacket. Available with tinned conductors. Jacket available in colors.

Application

For use in ASD/VFD applications.

Suitable for use in hazardous locations: Class I - Div 2,
       Class II - Div 2, Class III - Div 1 and 2

Standards

UL 1569
ICEA S-95-658/NEMA WC-70
Flame Rated: IEEE 383 (70,000 BTU), ICEA T-29-520 (210,000 BTU),
      
IEEE 1202/CSA FT-4, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry
Cold Temperature Rated at -25°C
Sunlight and Oil Resistant II
Jacket Direct Burial (includes encasement in concrete)
Color Code: Method 4
RoHS Compliant

ISOROHSMade in the USAREACHRockwell
VIEW PRODUCT TABLE DATA

Part Number

 

Size

(AWG or Kcmil)

Strand

(no.)

Insulation Thickness

(mils)

Grounding Conductors

(AWG)

Diameter over Armor

(in.)

PVC Jacket Thickness

(mils)

Approx. Diameter Overall

(in.)

Approx. Net Weight

(lb./1000')

Ampacity**

(30°C ambient) 90°C Wet/Dry

ASDGAP14/3

14*

  7

45

3-#14

0.57

50

0.67

     336

  25

ASDGAP12/3

12*

  7

45

3-#14

0.63

50

0.73

     394

  30

ASDGAP10/3

10*

  7

45

3-#14

0.67

50

0.77

     458

  40

ASDGAP8/3

8*

  7

45

3-#14

0.73

50

0.83

     556

  55

ASDGAP6/3

6

  7

45

3-#12

0.81

50

0.91

     725

  75

ASDGAP4/3

4

  7

45

3-#10

0.91

50

1.01

     977

  95

ASDGAP3/3

3

  7

45

3-#10

0.97

50

1.07

  1,120

115

ASDGAP2/3

2

  7

45

3-#8

1.03

50

1.13

  1,348

130

ASDGAP1/3

1

19

55

3-#8

1.15

50

1.25

  1,607

145

ASDGAP1/03

1/0

19

55

3-#6

1.31

50

1.41

  2,089

170

ASDGAP2/03

2/0

19

55

3-#6

1.41

50

1.51

  2,436

195

ASDGAP3/03

3/0

19

55

3-#4

1.51

60

1.63

  3,023

225

ASDGAP4/03

4/0

19

55

3-#4

1.63

60

1.75

  3,553

260

ASDGAP250/3

250

37

65

3-#4

1.81

60

1.93

  4,072

290

ASDGAP350/3

350

37

65

3-#2

2.03

60

2.15

  5,447

350

ASDGAP500/3

500

37

65

3-#1

2.29

75

2.44

  7,346

430

ASDGAP600/3

600

61

80

3-1/0

2.55

75

2.70

  8,799

475

ASDGAP750/3

750

61

80

3-2/0

2.77

75

2.92

10,692

535

*UL Listed Only
**Per NEC Table 310.15 (B)(16). NOTE: The data shown is approximate and subject to standard industry tolerances.

 Rep Login

 

CONTACT US

Your Name:

Email:

Phone:

Location (Zip Code):

Company:

Market:

Message: