SERVICEDRIVE®

ASD/VFD JACKETED MC

RHW-2 or RWU90

1,000/2,000 Volt Copper

Patented for use with ServiceDrive® connector and termination kit.

Description

3 conductors, stranded, insulated with heat and moisture resistant crosslinked polyethylene (type RHW-2 or RWU90), phase identified and cabled with suitable fillers and 3 symmetrical bare copper ground conductors. Cable core covered with binder tape, 5-mil helical copper tape shield, aluminum or galvanized steel interlocked armor with overall black PVC jacket. Available with CPE or EnviroPlus® (LSZH jacket).

Application

For use in ASD/VFD applications.

Suitable for use in hazardous locations: Class I - Div 2,
       Class II - Div 2, Class III - Div 1 and 2

Standards

UL 1569
ICEA S-95-658/NEMA WC-70
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4,
       UL 1685, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry
Sunlight Resistant
Direct Burial
Color Code: Black and Numbered
RoHS Compliant

ISOROHSMade in the USAREACHRockwell
VIEW PRODUCT TABLE DATA

Part Number

 

Size

(AWG or Kcmil)

Strand

(no.)

Insulation Thickness

(mils)

Grounding Conductors

(AWG)

Diameter Over Armor

(in.)

Jacket Thickness

(mils)

Approx. Diameter Overall

(in.)

Approx. Net Weight

(lb./1000')

Ampacity**

(30°C ambient) 90°C Wet/Dry

ASDGAP2K14/3

 14*

  7

  60

3-#14

0.65

50

0.75

     391

  25

ASDGAP2K12/3

 12*

  7

  60

3-#14

0.69

50

0.79

     442

  30

ASDGAP2K10/3

 10*

  7

  60

3-#14

0.73

50

0.83

     506

  40

ASDGAP2K8/3

  8*

  7

  80

3-#14

0.89

50

0.99

     686

  55

ASDGAP2K6/3

6

  7

  85

3-#12

0.99

50

1.09

     889

  75

ASDGAP2K4/3

4

  7

  85

3-#10

1.09

50

1.19

  1,153

  95

ASDGAP2K3/3

3

  7

  85

3-#10

1.15

50

1.25

  1,301

110

ASDGAP2K2/3

2

  7

  85

3-#8

1.27

50

1.37

  1,645

130

ASDGAP2K1/3

1

19

105

3-#8

1.43

50

1.53

  1,981

150

ASDGAP2K1/03

1/0

19

105

3-#6

1.51

60

1.63

  2,387

170

ASDGAP2K2/03

2/0

19

105

3-#6

1.61

60

1.73

  2,750

195

ASDGAP2K3/03

3/0

19

105

3-#4

1.73

60

1.85

   3,332

225

ASDGAP2K4/03

4/0

19

105

3-#4

1.85

60

1.97

  3,879

260

ASDGAP2K250/3

250

37

120

3-#4

2.05

60

2.17

  4,455

290

ASDGAP2K350/3

350

37

120

3-#2

2.27

75

2.42

  5,930

350

ASDGAP2K500/3

500

37

120

3-#1

2.53

75

2.68

  7,807

430

ASDGAP2K600/3

600

61

135

3-1/0

2.85

75

3.00

  9,323

475

ASDGAP2K750/3

750

61

135

3-2/0

3.01

85

3.18

11,278

535

* UL Listed Only
**Per NEC Table 310.15 (B)(16).
NOTE: The data shown is approximate and subject to standard industry tolerances.