SERVICEDRIVE®

VFD CABLE (ACWU90)

RWU90/PVC

1,000 Volt Copper

*Patented for use with ServiceDrive® connector and termination kit.

Description

3 conductors, stranded, insulated with heat and moisture resistant crosslinked polyethylene (type RWU90), phase identified and cabled with suitable fillers and 3 symmetrical bare copper ground conductors. Cable core covered with binder tape, 5-mil helical copper tape shield, aluminum or galvanized steel interlocked armor with overall black PVC jacket. Available with CPE jacket. Available with 50% grounds*.

Application

For use in ASD/VFD applications.

Suitable for use in hazardous locations: Class I - Div 2,
       Class II - Div 2, Class III - Div 1 and 2

Standards

CSA C22.2 #51/#174
ICEA S-95-658/NEMA WC-70
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4,
       UL 1685, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry
Sunlight Resistant
Direct Burial
Color Code: Black and Numbered
RoHS Compliant

VIEW PRODUCT TABLE DATA

Part Number

 

Size

(AWG or Kcmil)

Strand

(no.)

Insulation Thickness

(mils)

Grounding Conductors

(AWG)

Diameter Over Armor

(in.)

Jacket Thickness

(mils)

Approx. Diameter Overall

(in.)

Approx. Net Weight

(lb./1000')

Ampacity**

(30°C ambient) 90°C Wet/Dry

VFD2KGP6/3

6

  7

  85

3-#12

0.99

50

1.09

     862

  75

VFD2KGP4/3

4

  7

  85

3-#10

1.09

50

1.19

  1,119

  95

VFD2KGP3/3

3

  7

  85

3-#10

1.15

50

1.25

  1,262

110

VFD2KGP2/3

2

  7

  85

3-#10

1.27

50

1.37

  1,545

130

VFD2KGP1/3

1

19

105

3-#10

1.43

50

1.53

  1,864

150

VFD2KGP1/03

1/0

19

105

3-#10

1.51

60

1.63

  2,173

170

VFD2KGP2/03

2/0

19

105

3-#10

1.61

60

1.73

  2,522

195

VFD2KGP3/03

3/0

19

105

3-#8

1.73

60

1.85

   3,011

225

VFD2KGP4/03

4/0

19

105

3-#8

1.85

60

1.97

  3,537

260

VFD2KGP250/3

250

37

120

3-#8

1.99

60

2.11

  4,167

290

VFD2KGP350/3

350

37

120

3-#6

2.21

60

2.33

  5,433

350

VFD2KGP500/3

500

37

120

3-#6

2.47

75

2.62

  7,219

430

VFD2KGP600/3

600

61

135

3-#6

2.85

75

3.00

  8,615

475

VFD2KGP750/3

750

61

135

3-#4

3.01

85

3.18

10,461

535

**Per NEC Table 310.15 (B)(16).
NOTE: The data shown is approximate and subject to standard industry tolerances.