ARMORED CABLE

JACKETED MC

XHHW-2/EnviroPlus®

600 Volt Copper, Zero Halogen, Limited Smoke

3 Conductor, Factory Mutual Group 1

Description

3 conductors, stranded, insulated with heat and moisture resistant crosslinked polyethylene (type XHHW-2), phase identified and cabled with suitable fillers (as necessary) and bare copper ground conductor. Cable core is covered with binder tape and aluminum or galvanized steel interlocked armor, with zero halogen, limited smoke, zero lead jacket. Available with tinned conductors.

Application

Suitable for use in hazardous locations: Class I - Div 2, Class II - Div 2

Standards

UL1569
ICEA S-95-658/NEMA WC-70
Flame Rated: IEEE 383 (70,000 BTU), IEEE 1202/CSA FT-4,
       UL 1685 and UL 1581, Two-hour Firewall
Temperature Rated at 90°C Wet/Dry, Cold Temperature Rated at -40°C
Sunlight Resistant
Direct Burial (includes encasement in concrete)
Color Code: Method 4 (K2 on #8; other colors available)
Zero Halogen, Limited Smoke Jacket
RoHS Compliant

 

ISOROHSUSAREACHLEEDFM
VIEW PRODUCT DATA TABLE

Part Number

 

Size

(AWG or Kcmil)

Strand

(no.)

Insulation

Thickness

(mils)

Grounding

Conductor

(AWG)

Diameter

Over Armor

(in.)

Jacket

Thickness

(mils)

Approx.

Diameter Overall

(in.)

Approx.

Net Weight

Aluminum Armor

(lb./1000')

Approx.

Net Weight

Galvanized Armor

(lb./1000')

Ampacity*

(30°C ambient) 90°C Wet/Dry

AANH8/3

8

  7

45

10

0.73

50

0.83

     405

     489

  55

AANH6/3

6

  7

45

  8

0.81

50

0.91

     547

     643

  75

AANH4/3

4

  7

45

  8

0.91

50

1.01

     733

     854

  95

AANH3/3

3

  7

45

  6

0.97

50

1.07

     889

  1,011

115

AANH2/3

2

  7

45

  6

1.03

50

1.13

  1,044

  1,175

130

AANH1/3

1

19

55

  6

1.15

50

1.25

  1,264

  1,414

145

AANH1/03

1/0

19

55

  6

1.31

50

1.41

  1,548

  1,782

170

AANH2/03

2/0

19

55

  6

1.37

50

1.47

  1,843

  2,110

195

AANH3/03

3/0

19

55

  4

1.51

60

1.63

  2,311

  2,567

225

AANH4/03

4/0

19

55

  4

1.63

60

1.75

  2,785

  3,102

260

AANH250/3

250

37

65

  4

1.81

60

1.93

  3,337

  3,695

290

AANH350/3

350

37

65

  3

2.03

60

2.15

  4,303

  4,723

350

AANH500/3

500

37

65

  2

2.29

75

2.44

  5,956

  6,425

430

AANH600/3

600

61

80

  2

2.55

75

2.70

  7,074

  7,603

475

AANH750/3

750

61

80

  1

2.77

75

2.92

  8,658

  9,249

535

*Per NEC Table 310.15 (B)(16). Four-conductor ampacity assumes three are hot and one is neutral. NOTE: The data shown is approximate and subject to standard industry tolerances.

 

 Rep Login

 

CONTACT US

Your Name:

Email:

Phone:

Location (Zip Code):

Company:

Market:

Message: