TWISTED CABLE

PREASSEMBLED AERIAL

MV-105, Jacketed EPR

5,000 Volt Copper, Shielded

Description

Class B stranded copper, extruded semi-conductor shield, insulated with heat and moisture resistant EPR, copper shield (stranded or tape), with conductor jacket (PVC, CPE, etc.). Conductors are cabled with a left hand lay and laid parallel to a 30% EHS copperweld messenger then bound with a flat copper binding strap. Available with galvanized or stainless steel messengers, PVC coated copper or PVC coated stainless steel strap.

Standards

UL 1072 (single conductors)
ICEA S-93-639/NEMA WC-74
Sunlight Resistant
RoHS Compliant

ISORoHSUSAREACH
VIEW PRODUCT DATA TABLE

Part Number

 

Size

(AWG or Kcmil)

Strand

(no.)

Insulation Thickness

(mils)

Jacket Thickness

(mils)

Messenger Size **

(in.)

Messenger Size**

Strand (no.)

Approx. Diameter Overall

(in.)

Approx. Net Weight

(lb./1000')

Ampacity*

(40°C ambient)

AR5/16C5KS6/3E

6

7

115

60

5/16

7

1.76

  1,250

  88

AR5/16C5KS4/3E

4

7

115

60

5/16

7

1.88

  1,500

115

AR5/16C5KS2/3E

2

7

115

60

5/16

7

1.99

  1,795

154

AR5/16C5KS1/03E

1/0

19

115

80

5/16

7

2.27

  2,418

205

AR3/8C5KS2/03E

2/0

19

115

80

3/8

7

2.46

  2,883

240

AR1/2C5KS4/03E

4/0

19

115

80

1/2

7

2.75

  3,975

320

AR9/16C5KS250/3E

250

37

115

80

9/16

7

2.94

  4,592

355

AR9/16C5KS350/3E

350

37

115

80

9/16

7

3.16

  5,687

440

AR9/16C5KS500/3E

500

37

115

80

9/16

7

3.48

  7,382

545

AR9/16C5KS750/3E

750

61

115

80

9/16

7

3.89

10,137

685

*Per NEC Table 310.60 (C)(71). **Messenger size based on 150’ span with sag of 2.5 ft. NOTE: The data shown is approximate and subject to standard industry tolerances.